FIELDPIECE

DMM, TEMP, MFD, B/L MULTIMETRO

DMM, TEMP, MFD, B/L MULTIMETRO

SKU: HS36

PRODUCT TYPE: Digital Multimeters

Expedited Shipping

Ver todos los detalles

Features & Specifications

Expandable. Dependable. Practically indispensable.

The Perfect Fit for HVACR.

- Works with any accessory head
- Non-contact voltage
- 400 AAC with included clamp
- Temperature up to 1000°F
- Convenient lead storage
- Safe one-handed testing

The Fieldpiece top of the line True RMS Stick Meter, the HS36 includes the ranges you use everyday for HVAC/R field service plus includes a bright blue backlight and True RMS. Like the rest of the HS30 series, the HS36 comes equipped with a magnetic hanger, along with detachable silicone test leads and alligator clip probe tips for remote and easy one-handed testing, as well as the full set of built-in safety features. This auto-ranging stick meter also includes a bar graph on the LCD for an analog feel. Technicians who prefer our expandable stick meters tell us this is the best digital multimeter for HVAC/R field Service.

Features and Benefits
The HS meter series is unlike any other found in HVAC/R. Fieldpiece incorporates a number of safety features, both those you can and can t see, into our meters. In addition, the HS series accepts modular test instrument accessory heads. The HS36 is the top of the line stick meter. It includes the features and benefits that technicians tell us they need to do their job easier, better and faster:

Non-contact Voltage
With the red NCV tab on the tip of the meter close to an AC voltage, press and hold the NCV button. The NCV LED will light and the beeper will beep. The closer you get to AC voltage, the louder the beep. The NCV function is sensitive enough to detect 24VAC on thermostats.

High Voltage and Continuity Indicators
In any VAC/VDC range, when you touch a voltage greater than 30V, the beeper will beep and the red Hi-V LED will signal you. BE CAREFUL! The continuity beeper and green LED tell you if the circuit you re testing is open or closed (using the switch position to the right of OFF).

Microamps
For measuring the flame diode current in a heater control.

Capacitance
For motor-start and motor-run capacitors. Disconnect the capacitor from power first. Short the terminals to discharge the capacitors. Disconnect any resistors that might be between the terminals of the capacitor.

MIN/MAX
Press MIN/MAX once to begin recording MIN and MAX. Press MIN/MAX to select current reading s MIN or MAX. Hold down for 2 seconds to exit MIN/MAX function.

Temperature
Plug any K-type thermocouple directly into the meter to measure temperature. Temperature measurement will be accurate even in fast changing environments because of excellent temperature compensation. One thermocouple is included. No adapter is required.

Silicone Leads with Detachable Probe Tips
Because the wire insulation is silicone the leads will stay flexible in cold weather and will not melt if bumped by a soldering iron. When testing electrical circuits with two hands, there is a risk that a careless mistake may complete a circuit through your body and potentially cause death or injury. Detachable probes tips and the modular design of the HS36 allow you to plug V lead tip into the top of the meter, connect an alligator lead tip to COM and ground, and perform a one-hand test more easily than most any meter on the market.

And More:
Rugged ABS case with rubberized bumpers.
Built-in magnetic hanger allows you to test with one hand or no-hands.
Built-in lead storage.
Ergonomic shape fits naturally in your hand.
Auto power-off (APO) to conserve battery life.

Display: 3¾ digit liquid crystal display (LCD) with a maximum reading of 3999.
Analog bar graph: 41 segments with measurements 20 times per second.
Overrange: "OL" mark indication.
Auto power off: 30 minutes.
Operating environment: 32 to 122°F (0 to 50°C) at <70% R.H.
Storage temperature: -4 to 140°F (-20 to 60°C), 0 to 80% R.H. with battery removed.
Accuracy: Specifications good in ambient conditions of 73°F ±9°F (23°C ±5°C), <75% relative humidity.
Temperature coefficient: 0.1×(specified accuracy) per °F/°C. (32 to 64°F (0 to 18°C), 82 to 122°F(28 to 50°C)).
Power: Single standard 9-volt battery, NEDA 1604, JIS 006P, IEC 6F22.
Battery life: 300 hours typical with alkaline.
Accessories: One pair test leads, one pair alligator clips, k-type thermocouple, 9V battery (installed), and operating instructions.
Safety: UL,CE,Cat III600V,UL61010-1,IEC/EN61010-1.

Temperature
Range: -30 to 1000°F (-34 to 538°C)
Resolution: 0.1°F/°C
Accuracy: ±1°F, 32 to 120°F (0 to 49°C), ±1% + 1.5°F, -4 to 750°F (-20 to 399°C), ±2% + 4°F, -30 to -4°F (-34 to -20°C), ±2% + 4°F, 750 to 1000°F (399 to 538°C)
Sensor type: K-type thermocouple
Overload protection: 60 VDC or 30 VAC rms

Continuity
Audible indication: Less than 40O
Response time: 500ms
Green LED will be on continuously.
Overload protection: 500VDC or AC rms

DC Volts
Ranges: 400mV, 4000mV, 40V, 400V, 600V
Resolution: 0.1mV
Accuracy: ±(0.5% rdg + 2 dgt)
Input impedance: 3MO on V inputs, 10MO on mV input
Overload protection: 600VDC or AC rms
Transient protection: 6kV for 10µ sec

AC Volts (50Hz - 500Hz)
Ranges: 400mV, 4V, 40V, 400V, 600V
Conversion: True RMS (HS36), average (HS35)
Crest factor: Less than or equal to 3 (HS36)
Resolution: 0.1mV
Accuracy: ±(1.2% rdg + 5 dgts) 50Hz ~ 60Hz on 400mV range ±(1.5% rdg + 5 dgts) ±(2% rdg + 5 dgts) on 600V range
Input impedance: 3MO
Overload protection: 600V DC or AC rms
Transient protection: 6kV for 10µ sec

DC Current
Ranges: 400µA, 4000µA
Resolution: 0.1µA
Accuracy: ±(1.0% rdg + 2 dgt)
Voltage burden: 1V, (8V on 4000µA range)
Overload protection: 500V DC or AC rms

Resistance
Ranges: 400O, 4kO, 40kO, 400kO, 4MO, 40MO
Resolution: 0.1O
Accuracy: ±(1.0% rdg + 4 dgts) on 400O to 400kO ranges ±(1.5% rdg + 4 dgts) on 4MO range ±(3.0% rdg + 5 dgts) on 40MO range
Open circuit volts: -0.45VDC typical, (-1.2VDC on 400O range)
Overload protection: 500VDC or AC rms

Capacitance
Range: 400µF
Resolution: 0.1µF
Accuracy: ±(3% rdg + 5 dgts)
Overload protection: 500V DC or AC rms

Frequency
Ranges: 4k, 40k, 400k, 4M, 40MHz
Resolution: 1Hz
Accuracy: ±(0.1% rdg + 3 dgts)
Sensitivity: 10Hz ~ 4MHz: > 1Vrms, 4MHz ~ 40MHz: > 2Vrms, <5Vrms
Minimum pulse width: > 25ns
Duty cycle limits: > 30% and < 70%
Overload protection: 500VDC or AC rms

Inlcudes:
Expandable True RMS Stick Multimeter with Backlight - HS36
400A Amp Clamp Accessory - ACH4
Deluxe Silicone Test Leads - ADLS2
Short Alligator Lead Extensions - ASA2
Deluxe Meter Case - ANC1
9-Volt battery (installed)
Operator’s manual